SMCM1L-225H/4300

Short Description:

SMCM1L-225H/4300 Molded case circuit breaker Applications and functions • Incoming and outgoing function in distribution systems Switching and protection devices for motors, transformers and Disconnect or units with feai an emergency mechanisms with ld<eabte rotary operating Avail^le in the following Power protection: the designed for the protection of cables, leads and non-motor loads Motor protection: the overload and sh<xt-circut retaases are designed for optimized protection...


  • FOB Price: US $0.5 - 9,999 / Piece
  • Min.Order Quantity: 100 Piece/Pieces
  • Supply Ability: 10000 Piece/Pieces per Month
  • Port: Shenzhen
  • Payment Terms: L/C,D/A,D/P,T/T
  • Product Detail

    Product Tags

    SMCM1L-225H4300.jpg

    塑壳t1.jpg

    塑壳t2.jpg

    塑壳t3.jpg

    塑壳t4.jpg

    塑壳t5.jpg

    塑壳t6.jpg

    SMCM1L-225H/4300 Molded case circuit breaker Applications and functions

    • Incoming and outgoing function in distribution systems Switching and protection devices for motors, transformers and

    Disconnect or units with feai an emergency mechanisms with ld<eabte rotary operating Avail^le in the following Power protection: the

    designed for the protection of cables, leads and non-motor loads Motor protection: the overload and sh<xt-circut retaases are designed for optimized protection and direct-on-Hne starting of induction squirrel-cage motors. The circuit breakers for motor protection are susceptible to phase failure and feature an adjustable trip class

    • There Is no frame E and F for motor protection.

    1 Only M type (medium breaking capacity type) has 4 poles:

    4A: N-poie fixed without over-current release unit, it has been connected all atoog, and does not act with other three poles to turn on or off.

    4B: N-pole fixed without over-current release unit, it acts with other three poles.

    4C: N-poie fixed with over-current release unit, it acts with other three poles.

    4D: N-poie fixed with over-current retease unit, it has been

    Ked all adong, and does not act with other

    Technical Specifications

    Type SMCM1-63 SMCM1-100 SMCM1-225 SMCM1-400 SMCM1-630 SMCM1-800
    Stanclards IEC 60947-2 IEC 60947-2 IEC 60947-2 IEC 60947-2 IEC 60947-2 IEC 60947-2
    Approval IEC 60947-4-1 IEC 60947-4-1 IEC 60947-4-1 IEC 60947-4-1 IEC 60947-4*1 IEC 60947*4-1
    Frame type A B C D E F
    Class of breaking capacity L M L M H L M H L M H L M H M H
    Number of potes 3 3.4 3 3.4 3 3 3,4 3 3 3.4 3 3 3,4 3 3 3
    Frame Cunrenl Inm (A) 63 100 225 400 630 800
    Rated current In (A) 10.16.20.25. 16. 20.25.32 100,125.160 225.250.315 400.500 630.700
    Rated insulating voltage Ui (V) 32.40, 50. 63 40, 50. 63. 80.100 180. 200, 225 360.400 630 800
    500 800 800 800 800 800
    Rated operating vottage, Ue (V) 400 400 690 400 400 690 400 400 690 400 400 690 400 690 400
    Rated frequency 〇Hz) 50/60 QO/GO 50/60 50/60 50/60 5O/Q0
    Rated miputsed withstand voltage. Uimp (kV) 6 8 8 8 8 8
    Rated uttimate short-circuit breaking capacity, leu
    (AC) 50-60 Hz 400 VO-CO(kA) 25 50 35 50 85

    35 50

    85 50 65 100 50 65 100 65 100
    (AC) 50-60 H2 690 V O-CO (KA) - - - 20 -

    -20

    - - 20 - - 20 - 20 -
    Rated operating short-circut breaking capacity.lcs
    (AC) 50-60 Hz 400 V O-CO-CO (kA) 18 36 22 35 50

    22 36

    50 36 42 65 35 42 65 42 66
    (AC) 50-60 Hz 690 V O-CO-CO (kA) - 10 -

    10

    - - 10 - 10 15
    Mechanical life (times) 8000 8000 8000 7600 7500 7500
    Electrical life (times.) 1500 1500 1000 1000 1000 500
    Rashover distance (mm) Thermal magnetic release s50 s50 s50 s50 s100 s100■
    Electronic release -
    Utilization category {IEC 60947-2} A A A A A A
    Under-voitage reiease
    Shunt-retease
    Auxiliary contact _
    Alarm Contact
    Weight
    Ambient temperature -5 to +40°C . max. 95% humtdily
    Storage temperature -40 to +75#C
    Attitude (Max) 2000

     

     

    Normal working envimoment

    Attitude

    The rated perfornoance of the circuit breaker does not change up to 2000 meters. Beyond this altitude, the performance of the circuit breaker is subjest to derating, s

    Temperature

    Storage: -40°C to +70°C Operating: -5°C to +40°C

    In case the drcuit breaker operates at higher temperatures than +40°C, the current-carrying capacity of the circuit breaker may be lower than the rated current-carry capacity at the reference temperature, therefore the derating coeffrcients must be applied, see the derating coeffictents table on page A/00.

    Relative humidity

    When maximum temperature is 4〇°C, relative humidity shall be less than 50%.

    When the temperature is relative low, the relative hu巾idlty is allowed to be higher.

    Condensation caused by change of temperature shall be taken special measures.

    Pollution level 3

    Installation category Main circuit: III

    ^jxiliary circurt and control circuit: II Installation environment

    Horizontal or vertical, maximum inclination: 22.5 °.

    Resistance to moist air. satt mist and oil mist.

    Installed in an environment which is not enough to erode the metal or to destroy the insulating gas and without explosive danger. Installaed in an environment without attack from rain and snow.

    Applications and functions

    • Protection of plant and equipment against overload or damage by ground faults (ground-fault protection)

    Protection against tire hazard caused by insulation faults Switching and protection devices for motors, transformersar>d capacitors

    • Disconnector units with features for stopping and switching off In an emergency in conjunction with lockable rotary operating mechanisms and terminal covers.

    Technical specifications

    Frame type A B C D
    Standards IEC 60947-2 IEC 60947-4-1 IEC 60947-2 IEC 60947-2 IEC 60947-2
    IEC 60947-4-1 IEC 60947-4-1 IEC 60947-4-1
    Number 〇( poles Frame Cuneni Inm 3.4 3.4 3,4 3.4

    A

    100 225 4〇〇 630
    Rated current In

    A

    16, 20.25.32.4! 0 100,125,140,160 225,250,315 400,500,630
    50, 63,80.100 180. 200, 225 350.400
    Rated residual currents (An

    mA

    100. 300. 500,1000 100. 300, 500,1000 100,300,500 100.300,500,100
    Rated insuiatiog voyage LK Rated operating voltage, Ue 800 800 800 800

    V

    400 400 400 400
    Rated frequency

    Hz

    50/60 50/60 50/60 50/60
    Rated impulsed withstand voltage. Uimp

    kV

    8 8 8 8
    Rated intimate short-circuit breaking capacity, leu (AC) 50-60 Hz 400V O-CO

    kA

    35 35 50 80
    Rated operating short-circuit breaking capacity.lcs (AC) 50-60 Hz 400V O-CO-CO

    kA

    22 25 35 35
    Mechanical Ufe

    times

    8500 7000 4000 4000
    Electrical life

    times

    1500 1000 1000 1000
    Ra$r>over cfestance

    mm

    £50 £50 s100 s100
    UTit2ati〇n categwy (IEC60947-2) A A
    Ambient temperature -5 to +40°C. ma> 95% humidity
    Storage temperature •40to+75*C

     

     

     